Section 205. Separation and ventilation of stairs  


Latest version.
  • 1.  All stairs and
      fire-stairs shall be completely separated  from  one  another  and  from
      every  elevator  or  other  shaft  by  fireproof  walls.   They shall be
      constructed of fireproof material throughout and shall contain  no  wood
      or  other  inflammable  material  of  any kind, except that handrails of
      hardwood may be provided.
        2. Access to stairs and fire-stairs from any public vestibule or other
      public hall shall be through fireproof doors and  assemblies,  with  the
      doors  self-closing  and  at  least three feet wide, or through pairs of
      such doors at least four feet wide, containing in either  case  a  fixed
      sash glazed with wire glass at least one-quarter inch thick and at least
      three hundred sixty square inches in area.
        3.  At  the highest level of every stair and fire-stair there shall be
      provided a window or a skylight. At such termination, there  shall  also
      be  an  opening  of  at least one hundred forty-four square inches which
      shall communicate directly to the outer air, which opening may be a part
      of such window or skylight. Except as  herein  provided,  such  skylight
      shall  ccomply  with  the  provisions  of subdivision two of section one
      hundred eight.