Section 27-2038. Electric lighting fixtures in certain public parts of dwellings; fixtures and lights required  


Latest version.
  • a. In every  multiple  dwelling  and   tenant-occupied  two-family  dwelling,  the  owner  shall  provide
      electric lighting fixtures for every public hall, stair, fire stair  and
      fire   tower   on   every   floor,  in  accordance  with  the  following
      requirements:
        (1) If an incandescent lighting  fixture  is  provided,  it  shall  be
      capable  of providing illumination of at least ten watts per twenty-five
      square feet of floor area or fraction  thereof.  Each  lighting  fixture
      shall  be  provided  with one or more lights of a total of not less than
      sixty watts. Where, under this requirement,  the  number  of  watts  per
      fixture  would exceed one hundred, one or more additional fixtures shall
      be provided and shall be located as may be prescribed by the department,
      except where the distance from the fixture to the farthest  intersecting
      wall does not exceed twenty feet.
        (2) If a fluorescent lighting fixture is provided, it shall be capable
      of  providing illumination of at least four watts cool white fluorescent
      light per twenty-five square feet of floor  area  or  fraction  thereof.
      Each  lighting  fixture  shall  be provided with one or more lights of a
      total of not less than twenty watts. Where, under this requirement,  the
      number  of  watts per fixture would exceed forty, one or more additional
      fixtures shall be provided and shall be located as may be prescribed  by
      the  department,  except  where  the  distance  from  the fixture to the
      farthest intersecting wall does not exceed twenty feet.
        (3) In every multiple dwelling hereafter erected, in addition to other
      lighting  requirements,  a  sufficient   number   of   incandescent   or
      fluorescent  fixtures  shall  be  provided  so that the distance between
      fixtures is not more than thirty feet and so that no wall is  more  than
      fifteen feet distant from a fixture.
        b.  The  department  may  approve  electric lighting for public halls,
      stairs, fire stairs and fire towers  other  than  the  incandescent  and
      fluorescent  lighting  required in subdivision a of this section if such
      other method of electric lighting provides equivalent illumination,  and
      meets the requirements of the electrical code.
        c.   Notwithstanding  any  other  requirement  of  this  section,  the
      department may  require  fixtures  to  be  so  located,  and  additional
      fixtures  to  be  installed, in order to assure that every part of every
      public hall, stair, fire stair or fire tower is adequately lighted.