Section 27-423. Exit requirements  


Latest version.
  • In  every  room  containing  a boiler,
      furnace, or incinerator, the maximum  travel  distance  from  any  point
      within the room to an exit shall not exceed fifty feet. When two or more
      exits are so required, only the main exit shall comply with the size and
      construction  requirements  of subchapter six of this chapter. The other
      exit or exits may be noncombustible ladders or stairs  leading  to  exit
      openings not less than thirty-two inches by forty-eight inches.