Section 27-455. Sprinklers  


Latest version.
  • (a) Automatic sprinkler protection complying with
      the  construction  provisions  of  article  four of subchapter seventeen
      shall  be  provided  as  required  for  occupancy  group  B-1   or   B-2
      respectively,  except  that  in  existing buildings lawfully occupied as
      garages prior to December sixth, nineteen hundred  sixty-eight,  storage
      of  forty-five  thousand gallons or less of product having a flash point
      over one hundred degrees F (tag open cup) in the  cargo  space  of  tank
      truck   or  other  vehicles  approved  for  such  storage  by  the  fire
      commissioner, pending delivery, shall not be deemed to require sprinkler
      protection.
        (b)  Smoke  detection  or  thermostatic  alarm  with  central   office
      connection.  A  thermostatic  alarm  system  or  smoke  detection system
      equipped with a central  office  connection  complying  with  subchapter
      seventeen  of  this code, and reference standard RS-17-3 of the appendix
      to this code may be provided in lieu of the  sprinkler  system  required
      under  the preceding subdivision in existing buildings lawfully occupied
      as garages prior to December sixth, nineteen hundred  sixty-eight,  when
      the storage of fuel oils or other products having a flash point over one
      hundred  degrees  F  (tag  open cup) is twenty-two thousand five hundred
      gallons or more but not exceeding forty-five  thousand  gallons  in  the
      cargo  space  of tank trucks or other vehicles approved for such storage
      by the fire commissioner, pending delivery.
        (c) Portable fire fighting appliances, as the  fire  commissioner  may
      direct,  shall  be  provided  in existing buildings lawfully occupied as
      garages prior to December sixth, nineteen hundred sixty-eight, when  the
      storage  of  fuel  oils or other products, having a flash point over one
      hundred degrees F (tag open cup), in the cargo space of tank  trucks  or
      other  vehicles  approved  for  such  storage  by the fire commissioner,
      pending delivery, is less than twenty-two thousand five hundred gallons.