Section 27-353.2. Smoke protection for elevators in E occupancies  


Latest version.
  • For an
      elevator in a high rise building where such elevator serves four or more
      stories that contain space  classified  in  occupancy  Group  E  (office
      space),  inclusive of any lobby or entry level, such elevator shall meet
      the following requirements at every level served by  such  elevator  (i)
      for  such  buildings erected pursuant to new building applications filed
      on or after the effective date of this section, or  (ii)  where  two  or
      more new elevator shafts are installed in such buildings in existence on
      the effective date of this section:
        (a)  Elevator  vestibule  required.  At  every  floor  above  the main
      entrance floor where the fire command station is located, all  elevators
      shall  open  into an enclosed elevator vestibule. The elevator vestibule
      shall be  separated  from  the  building  occupancy  by  smoke  barriers
      extending from floor slab to floor slab.
        (b)   Permitted   penetrations.  Penetrations  in  addition  to  those
      permitted in section 27-353.3 (smoke barrier)  shall  be  provided  with
      smoke  dampers  as  defined in reference standard RS 13-1, except that a
      package pass through or communication opening not exceeding  one  square
      foot in area need not be provided with smoke dampers.
        (c)  Access  to  exits.  Access  to  an  exit on any floor through the
      enclosed elevator vestibule shall be permitted if the occupied areas  on
      that floor have access to at least one other required exit that does not
      require passing through the elevator vestibule.
        (d)  On  floors  with  a  floor  area of less than twenty-five hundred
      square feet, the  commissioner  may  accept  an  alternative  design  or
      construction  method that accomplishes the purposes of this section, or,
      if the commissioner determines that  compliance  with  this  section  is
      impracticable  in  whole  or  in part, the commissioner may authorize an
      exemption from the requirements of this section.