Section 27-330. Slow burning plastic
Latest version.
-
Slow burning plastic shall be of a material that burns no faster than two and one-half inches per minute in sheets 0.060 in. thick when tested in accordance with reference standard RS 5-12 or that is not consumed in less than two minutes when tested in accordance with reference standard RS 5-13. The thickness of the plastic material shall be determined by method "B" of reference standard RS 5-14.