Section 27-981. General requirements for smoke detecting devices


Latest version.
  • a. All
      smoke detecting devices required to be provided and  installed  pursuant
      to  this  article  shall  either  be  accepted  pursuant  to  rules  and
      regulations promulgated by the commissioner or be listed by a nationally
      recognized independent laboratory that maintains periodic inspections of
      production of  listed  equipment  and  whose  listing  states  that  the
      equipment   meets   nationally   recognized   standards.   To  meet  the
      requirements of  this  article,  such  laboratory  shall  be  one  which
      maintains  a  periodic  follow-up  service  of  the  devices  to  ensure
      compliance with the original listing.
        b. No device shall be deemed to be in compliance with  the  provisions
      of  this  article  unless  it  is  of  either  the ionization chamber or
      photo-electric type. Such  devices  shall  be  in  compliance  with  the
      requirements  of reference standard RS 17-11 and shall be installed in a
      manner consistent with the requirements of reference standard  RS  17-12
      except  that  devices  within  occupancy  group  J-1  shall be installed
      pursuant to rules and regulations promulgated by the commissioner.