Section 27-959. Siamese connections required  


Latest version.
  • (a) Where required.
        (1)  Siamese  connections shall be provided in accordance with section
      27-940  of  article  three  of  this  subchapter,  except  as   modified
      hereinafter.
        (2)  In below grade sprinkler systems for garage occupancies involving
      the storage or repair of motor vehicles, a siamese connection  shall  be
      provided  within  fifty  feet  of  every  exit or entrance used by motor
      vehicles.
        (3) Where partial sprinkler protection is required for storage spaces,
      one siamese connection shall be provided when more than thirty-six heads
      are  installed  in  one  fire  section.  Areas  subdivided,   when   the
      subdivisions  are totally enclosed by noncombustible construction having
      at least a two hour fire-resistance rating, shall be considered separate
      fire sections and the number of  heads  in  the  largest  section  shall
      determine the necessity for siamese connections.
        When  partial  sprinkler systems are installed to protect entire floor
      areas, siamese connections shall be provided in accordance with  section
      27-940 of article three of this subchapter.
        In  all  cases  where  partial  sprinkler  protection  is provided and
      siamese connections installed, metal signs shall  be  securely  fastened
      to,  or  above,  the  siamese  connection indicating the area protected.
      Where the building has two or more  frontages,  additional  metal  signs
      shall be installed indicating the location of the siamese connection.
        (4)  When  a  sprinkler  system supplies a group of buildings, siamese
      connections  shall  be  provided  for  each  building  as  required   by
      paragraphs one, two and three of this subdivision.
        (5) A single three-inch (seventy-six millimeter) inlet fire department
      connection  acceptable  to the fire commissioner may be provided for the
      sprinkler  system  in  lieu  of  each  required  siamese  connection  in
      buildings classified in occupancy group J-2 not exceeding six stories or
      seventy-five  feet in height and in spaces classified in occupancy group
      J-2 in buildings not exceeding  six  stories  or  seventy-five  feet  in
      height.
        (b)  Installation  and construction. The installation and construction
      of siamese connections shall be the same as required for fire  standpipe
      systems,  except  that  the  caps  of  each  automatic sprinkler siamese
      connection shall be painted green and the entire siamese connection of a
      nonautomatic sprinkler system shall be painted with aluminum paint,  and
      except  that  caps  of  each  siamese  connection  used  for combination
      standpipe and sprinkler  systems  shall  be  painted  yellow  and  signs
      provided  as  required  in  subdivision  (b) of section two of reference
      standard RS17-1.
        (c) A siamese connection need not be provided for a  sprinkler  system
      in one and two family dwellings.