Section 27-949. Protection of standpipe system  


Latest version.
  • (a)  All  parts  of the
      standpipe systems that may be exposed to frost shall be  protected  from
      freezing by any one of the following methods:
        (1)  The piping shall be frostproofed with insulation having a thermal
      conductance of 0.1 Btu/hr. per square foot of surface per degree F at  a
      mean  temperature of seventy to seventy-five degrees F. Insulation shall
      be protected to prevent water infiltration,  and  when  exposed  to  the
      weather  the insulation shall be covered with a forty-five pound roofing
      felt jacket or equivalent.
        (2) Steam or electric tracers may be  used  in  conjunction  with  the
      insulation.
        (b) Tanks subject to freezing temperatures shall be protected.