Section 27-946. Fire pumps  


Latest version.
  • (a) Additional water supply. Additional water
      supply shall be provided for standpipes in buildings over three  hundred
      feet  high.  The  primary  water supply to the standpipe system shall be
      supplemented by one or more manually operated fire pumps as follows:
        (1) Standpipe systems in buildings more than three hundred  feet  high
      shall have at least one seven hundred fifty gpm pump or two five hundred
      gpm  pumps. Pumps shall be capable of delivering their rated capacity at
      a pressure of fifty psig above the  normal  static  pressure  determined
      from  the highest hose outlet (except the roof manifold) in the building
      plus the frictional resistance through the pipe from  the  pump  to  the
      outlet.
        (2)  Where  a  group  of  two  or more buildings, whether connected or
      separated, are operated  under  a  single  ownership  and  one  or  more
      buildings  exceed  three  hundred feet in height, one fire pump shall be
      accepted as the supplemental supply for the group.  The  pump  shall  be
      installed  in  the building where the maintenance personnel are located,
      and a metal sign with one inch lettering  shall  be  installed  in  each
      building at all of the hose outlets on the entrance floor indicating the
      location of the fire pump.
        (b) Standpipe pump rooms and location.
        (1)  Fire  pumps  shall  be  installed  at the entrance floor level or
      below, in rooms enclosed by noncombustible  construction  having  a  two
      hour  fire-resistance rating and that are adequately heated, ventilated,
      lighted, and drained. The pump room shall  have  access  to  the  street
      level  by a direct opening to a street or a court, or by a passageway or
      stairway having a fire-resistance rating of at least two hours.
        (2) No person shall install other machinery or mechanical equipment in
      a fire pump room, unless the building is of construction class  IA,  IB,
      or IC.
        (3)  No  person  shall  place  or  install  any equipment containing a
      refrigerant classified in groups A1, A2, A3, B1, B2 or B3 in  subchapter
      thirteen  of  this  chapter,  or  place  or  install  gas  piping or gas
      consuming devices or any other equipment within any space housing a fire
      pump that would create a hazardous condition.
        (c) Power supply for standpipe fire pumps. The type of fire  pump  and
      prime  mover  used  in  a  standpipe  system  shall  be suitable for the
      required service in a standpipe system provided for fire department use.
      If the prime mover employs any form of  power  other  than  an  electric
      current  supplied  by a public utility, the use thereof shall be subject
      to the approval of the commissioner. Electrical power to the motor shall
      be taken from the street side of the house service switch.
        (d) Combined use of fire pumps for standpipe and  automatic  sprinkler
      systems.  A fire pump that furnishes the required auxiliary water supply
      either to a standpipe system or to an automatic sprinkler  system  shall
      be  accepted  as  furnishing the corresponding water supply to the other
      system if such pump is in the same premises, provided that in every such
      case of combined use,  suitable  relief  and  shutoff  valves  shall  be
      installed so as to prevent the water pressure on the automatic sprinkler
      system  resulting  from  any  required  operation  of  the  pump for the
      standpipe system from becoming greater  than  one  hundred  seventy-five
      psig.