Section 27-934. Standpipe systems in structures being erected or demolished
Latest version.
-
(a) During construction or demolition of any structure for which a standpipe system is required, provision shall be made for the use of such standpipe by the fire department in accordance with the provisions of section 27-1014 of article one of subchapter nineteen and this subchapter. (b) Temporary risers shall be at least four inches in diameter for structures less than four hundred fifty feet high and at least six inches in diameter for structures four hundred fifty feet high or more. There shall be as many risers as will be, or were, required for the permanent system. Each such riser shall be connected to a cross connection that is supplied through siamese hose connections at the street level, and shall be equipped on each floor with a two and one-half inch hose outlet valve. The installations shall be made so that each riser, cross-connection, and branch line can be plugged or capped when work is not being done on the system. The location of the siamese hose connection shall be placarded, kept free from obstruction, and identified by a red light.