Section 27-932. When required  


Latest version.
  • (a) Wet standpipe systems shall be installed:
        (1)  In  all  buildings  or  portions thereof exceeding six stories or
      seventy-five feet in height, except that open parking  structures  shall
      not  require  installation  of a wet standpipe system unless they exceed
      ten parking levels or seventy-five feet in height.
        (2) In all portions of buildings two or more stories  in  height  that
      have a floor area of ten thousand square feet or more on any floor.
        (b)  Where  standpipes are required by the height and area limitations
      of subdivision (a) of this section, a  non-automatic  or  automatic  dry
      standpipe  system  may  be installed in lieu of the wet standpipe in all
      buildings classified in occupancy  group  G  not  over  six  stories  or
      seventy-five  feet  in height. A dry standpipe system shall be installed
      in all open parking structures which exceed  three  parking  levels  and
      contain not more than ten parking levels.
        (c)  A  standpipe system shall be installed in all buildings exceeding
      three stories in height that have an area exceeding seven thousand  five
      hundred  square  feet  on  any floor and where a standpipe system is not
      otherwise required by the provisions of this subchapter. A  nonautomatic
      or automatic dry system may be used in lieu of the wet standpipe.
        (d)  The  following  buildings  shall be exempt from the provisions of
      subdivisions (a), (b) and (c) of this section:
        (1) Buildings classified in occupancy groups F, G, H, and  J  that  do
      not  exceed  two  stories or thirty feet in height and an area of twenty
      thousand square feet on any floor and are provided with hand or portable
      fire extinguishers as required by the fire department.
        (2) Buildings classified in occupancy groups E, F, G, H,  and  J  that
      require  a wet standpipe as provided in paragraph two of subdivision (a)
      and subdivision (c) of this section but not  exceeding  six  stories  or
      seventy-five  feet  in  height  and that are equipped throughout with an
      automatic wet or dry sprinkler system connected to a central supervisory
      station, and such system complies with the provision of this subchapter.