Section 27-930. Existing standpipes  


Latest version.
  • Standpipe systems existing on December
      sixth, nineteen hundred sixty-eight shall not be required to be  altered
      to conform to the provisions of this subchapter, except as follows:
        (a)  The  existing  installation  shall  meet  the  following  minimum
      requirements:
        (1) WATER SUPPLIES. There shall be a reserve of at  least  twenty-five
      hundred gallons of water in a gravity or pressure tank for exclusive use
      of  the  standpipe; or there shall be a direct connection to a city main
      meeting the requirements of section 27-945  of  article  three  of  this
      subchapter.
        (2) GRAVITY TANKS. The gravity tank or tanks shall be filled by direct
      city water connection or by an automatic fill pump at a rate of at least
      forty-five  gpm;  and  the  bottom of the tank shall be located at least
      eleven feet six inches above the highest  hose  outlet  under  the  main
      roof.
        (3)  HOSE  AND  HOSE  VALVES.  Hose  and  hose valves shall be in good
      serviceable condition. Hose valve wheel handles shall be within six feet
      six inches of the floors or stair landings or the wheel  handle  may  be
      within  two  feet  horizontally  from a stair tread and no more than six
      feet six inches vertically above the tread. Such  hose  may  be  omitted
      from  hose  racks  in existing buildings in occupancy group J-2 provided
      that the provisions of paragraph five  of  subdivision  (c)  of  section
      27-942 of article three of this subchapter are complied with.
        (4)  FIRE DEPARTMENT CONNECTIONS. There shall be a three inch by three
      inch siamese hose connection with approved caps, painted red.  The  word
      "Standpipe"  shall  be  cast in the body of the siamese connection or on
      metal plates that are secured to  the  riser  or  to  the  face  of  the
      building behind the siamese connection.
        (5)  NOZZLES.  A  five-eighths  inch  smooth  bore nozzle with two and
      one-half inch hose shall be provided where the hydrostatic  pressure  at
      the hose valve is less than ten psig.
        (6)  PROTECTION  FROM FREEZING. All parts of the standpipe system that
      are exposed to freezing  shall  be  protected  in  accordance  with  the
      requirements  of  subdivision  (a) of section 27-949 of article three of
      this subchapter.
        (7) PRESSURE  REDUCING  VALVES.  Pressure  reducing  valves  shall  be
      provided  as  required  by  section  27-944  of  article  three  of this
      subchapter.
        (8) DRIP VALVES. Drip valves shall be  provided  between  the  siamese
      connection and the check valve.
        (b) When the building requires additional standpipe protection because
      of  extension in height or in area, or the occupancy is changed to a use
      requiring additional protection, the new or altered part of  the  system
      shall comply with this subchapter.