Section 27-883. Gas equipment connected to chimneys  


Latest version.
  • Automatically controlled
      gas-fired  equipment  connected  to a chimney that also serves equipment
      for the combustion of solid or liquid fuel shall  be  equipped  with  an
      automatic  pilot.  A  gas-fired  equipment  vent connector and a chimney
      connector from equipment burning  another  fuel,  located  on  the  same
      floor, may be connected into the same chimney through separate openings,
      or  may  be  connected  through a single opening if joined by a suitable
      fitting located as close as practicable to the chimney. If two  or  more
      openings  are  provided  into  one  chimney,  they shall be at different
      levels.