Section 27-876. Chimneys for building service incinerators  


Latest version.
  • Chimneys for
      building service incinerators shall be constructed  in  accordance  with
      the  requirements  of  this  subchapter  for  high or medium temperature
      chimneys, based upon the temperature  of  the  flue  gases  leaving  the
      equipment,  except  that  no  reduction of flue gas temperature shall be
      recognized if such reduction is the result of using water  scrubbers  or
      barometric  dampers.  In  addition,  such chimneys shall comply with the
      following:
        (a) Chimneys shall extend through the roof and be open to the air.
        (b) Chimneys shall be provided with a spark arrester  as  required  in
      paragraph four of subdivision (a) of section 27-875 of this article.
        (c)  Incinerators  may discharge into chimneys serving other equipment
      provided such combined chimney  is  of  adequate  size  for  both  uses,
      conforms  to  construction  required  for  the  highest temperature, and
      adequate draft control equipment is provided for each  device  connected
      to the combined chimney.