Section 27-863. Chimney construction for low, medium, and high temperature equipment  


Latest version.
  • (a) Unlisted chimneys for low temperature equipment shall  be  constructed in accordance with table 15-4.
        (b)  Unlisted  chimneys  for  medium  temperature  equipment  shall be
      constructed in accordance with table 15-5.
        (c)  Unlisted  chimneys  for  high  temperature  equipment  shall   be
      constructed in accordance with table 15-6.
     
                (For table 15-4 see chapter 839 of the laws of 1986)
     
        Notes:
        a  Metal  chimneys  shall be of riveted, bolted or welded construction
      and made gas tight.
        b Exterior metal chimneys shall  be  galvanized,  or  painted  on  the
      exterior  surface with a heat resisting paint or be constructed of equal
      corrosion resistive alloys.
        c In buildings in residential occupancy group J-3, of four stories  or
      less,  and  in other buildings not over two stories high and not in high
      hazard occupancy group A, providing the flue areas are not more than 200
      sq. in. the walls of masonry or concrete chimneys may be  reduced  to  4
      in.  with  fire  clay  flue  lining.  Flue linings shall be set ahead of
      chimney walls, and carefully bedded in fire clay  mortar  or  in  cement
      mortar. Chimney walls shall be provided with mortar spacer ties every 10
      ft.  of  height.  Mortar  ties  shall  not be continuous around the flue
      linings.
     
            (For tables 15-5&15-6 see chapter 839 of the laws of 1986)