Section 27-863. Chimney construction for low, medium, and high temperature equipment
Latest version.
-
(a) Unlisted chimneys for low temperature equipment shall be constructed in accordance with table 15-4. (b) Unlisted chimneys for medium temperature equipment shall be constructed in accordance with table 15-5. (c) Unlisted chimneys for high temperature equipment shall be constructed in accordance with table 15-6. (For table 15-4 see chapter 839 of the laws of 1986) Notes: a Metal chimneys shall be of riveted, bolted or welded construction and made gas tight. b Exterior metal chimneys shall be galvanized, or painted on the exterior surface with a heat resisting paint or be constructed of equal corrosion resistive alloys. c In buildings in residential occupancy group J-3, of four stories or less, and in other buildings not over two stories high and not in high hazard occupancy group A, providing the flue areas are not more than 200 sq. in. the walls of masonry or concrete chimneys may be reduced to 4 in. with fire clay flue lining. Flue linings shall be set ahead of chimney walls, and carefully bedded in fire clay mortar or in cement mortar. Chimney walls shall be provided with mortar spacer ties every 10 ft. of height. Mortar ties shall not be continuous around the flue linings. (For tables 15-5&15-6 see chapter 839 of the laws of 1986)