Section 27-861. Metal chimneys  


Latest version.
  • (a) Exterior metal chimneys. Exterior metal
      chimneys constructed of steel shall be of adequate thickness  to  resist
      all  applied  loads  specified  in  subchapter nine of this chapter, but
      shall not be less than the thickness required in table 15-4.
        (b) Clearances for exterior metal chimneys. Metal chimneys erected  on
      the  exterior  of a building shall have sufficient clearance from a wall
      or frame of combustible construction  to  satisfy  the  requirements  of
      table  15-2  and  to permit inspection and maintenance operations on the
      chimney, and shall comply with the following minimum requirements:
        (1) Exterior metal chimneys over  eighteen  inches  in  diameter,  for
      equipment  of  any  operating  temperature, shall have a clearance of at
      least four inches, and those eighteen inches or less in  diameter  shall
      have  a  clearance  of  at  least two inches from a building wall of any
      combustible construction.
        (2) No portion of an exterior  metal  chimney  shall  be  nearer  than
      twenty-four  inches  to  any  door  or window or to any exit, or located
      where it would be  readily  accessible  to  the  public,  unless  it  is
      insulated  or  shielded  to avoid injury to any person coming in contact
      with the chimney.
     
       Table 15-2  Minimum Clearances Required from any Combustible Materials
     
      ========================================================================
                     ----------Classification of Equipment----------
                         Low           Medium               High
                     Temperature     Temperature         Temperature
      ------------------------------------------------------------------------
                         6"              24"                 24"
      ========================================================================
     
        (c) Enclosure of interior metal chimneys:
        (1) Every interior  metal  chimney  or  part  thereof  erected  within
      buildings  shall  be  enclosed with noncombustible construction having a
      fire resistance rating of not less than that prescribed in table 15-3 in
      all stories above the one in  which  the  equipment  served  thereby  is
      located.  Where  the metal chimney passes through a combustible roof, it
      shall be guarded by a noncombustible ventilating thimble  of  galvanized
      metal  or  equivalent noncombustible material that extends at least nine
      inches below and above the roof construction. The thimbles shall be of a
      size to provide clearances on all sides of the metal chimney of at least
      six inches for low temperature equipment and at  least  eighteen  inches
      for  medium  and  high  temperature  equipment  as defined in subchapter
      fourteen of this chapter. However, if the metal chimney is insulated and
      protected to prevent a  temperature  of  more  than  two  hundred  fifty
      degrees Fahrenheit on its exterior surface, the thimble clearance may be
      reduced by fifty percent.
        (2)  The enclosure around a metal chimney shall provide a space on all
      sides of the chimney to permit inspection  and  repair  for  the  entire
      chimney  height.  When  metal  chimneys  have  a  minimum  dimension  of
      twenty-four  inches  in  diameter  and  are  completely  jacketed   with
      noncombustible insulating material within the required enclosure, access
      to permit inspection and repair shall not be required.
        (3)  The  enclosing  construction shall be of noncombustible materials
      and shall have a fire resistance rating as required in  table  15-3  and
      shall  be without openings, except access openings equipped with opening
      protectives  constructed  in  accordance  with   the   requirements   of
      subchapter  five  of  this  chapter, at floor levels where necessary for
      complete inspection purposes.
    
        (4) The required  fire  resistance  ratings  of  table  15-3  for  the
      enclosure  of  a medium or high temperature metal chimney may be reduced
      by one hour if the chimney is insulated with an insulation adequate  for
      the  temperature  of  the  chimney  and  having at least a one hour fire
      resistance rating at all sections of the insulation.
     
             Table 15-3  Required Fire Resistance Ratings of Enclosures
                                 for Metal Chimneys
     
      ========================================================================
                                         Required Fire Resistance
          Chimney Classification            Rating of Enclosure
      ________________________________________________________________________
           Low temperature          1 Hr. for buildings under 5 stories
                                    2 Hr. for buildings 5 stories or more
           Medium temperature       2 Hr.
           High temperature         3 Hr.
      ========================================================================
     
      Note: Table  3-4  of  section  27-271 shall also be complied with in the
            construction of enclosures for metal chimneys.
     
        (d) Prohibited location. No interior metal chimney shall be carried up
      inside a ventilating duct unless such duct is constructed as required by
      this subchapter for metal chimneys, and only  when  such  duct  is  used
      solely  for  exhaust  venting  the  room or space in which the equipment
      served by the metal chimney is located.  Metal  chimneys  shall  not  be
      installed in air supply ducts.
        (e)  Unlisted  metal  chimneys  serving  residential  type or low heat
      appliances and producing flue gas having a temperature  below  350°F  at
      the  entrance to the chimney at full load or partial load shall be lined
      with acid and condensate resistant refractory material,  or  constructed
      of suitable stainless steel, or otherwise protected so as to minimize or
      prevent  condensation  or  corrosion  damage  as  required  in reference
      standard RS 15-14.
        (f) Steel chimneys for exterior use shall  be  insulated  and  weather
      sheathed  to maintain flue surface temperatures above the acid dew point
      in all parts of the system in accordance with subdivision (b) of section
      27-854.
        (g) Steel chimneys for interior  use  shall  be  insulated  to  ensure
      enclosure  temperatures  not in excess of 160°F on combustible materials
      in accordance with subdivision (a) of section 27-854.