Section 27-819. Furnace supports  


Latest version.
  • Floor furnaces shall be installed only in
      floors of noncombustible construction having at least a  two  hour  fire
      resistance  rating, except as provided for one- and two-family dwellings
      in section 27-823  of  this  article.  Floor  furnaces  shall  have  the
      following clearances:
        (a)  Pit  clearances. Floor furnaces, when other than gas-fired, shall
      be mounted independently of the floor grille with a six  inch  clearance
      at  the  bottom and a twelve inch clearance at the sides except that the
      clearance on the control side shall be at least eighteen inches.
        (b) Pit waterproofing. When there is likelihood of water rising  above
      the  bottom  clearance  of the unit, the pit shall be constructed with a
      watertight enclosure with the sides extending at least four inches above
      the ground level.