Section 27-761. Corridors  


Latest version.
  • Unless  natural  sources complying with section
      27-749 of article six of this subchapter provides  ventilating  openings
      equivalent  to  at  least  two  and  one-half percent of the floor area,
      corridors in buildings of occupancy groups H-1, J-1 and  J-2  more  than
      three  stories  in  height, shall be mechanically ventilated by a system
      supplying at least one-half cubic foot of outdoor  air  per  minute  per
      square  foot of floor area. When air conditioned, a part of the required
      supply may be recirculated as  equivalent  outdoor  air,  but  at  least
      thirty-three  and  one-third percent of the required air supply shall be
      actual outdoor air.