Section 27-740. Heating requirements  


Latest version.
  • All habitable or occupiable rooms or
      spaces, and all other rooms or spaces listed in  table  12-1,  shall  be
      provided  with  means  of heating in accordance with the requirements of
      this subchapter and reference standard RS 12-1. Heating systems shall be
      capable of producing the required temperatures listed in table 12-1 when
      the outdoor temperature is five degrees Fahrenheit and the wind velocity
      is fifteen mph. In highly exposed locations, provision shall be made for
      higher wind velocities. Heating equipment shall  not  be  required  when
      either of the following conditions exist:
        (a)  Where  the  occupancy is seasonal and the rooms or buildings will
      not be occupied between November first and May first  of  the  following
      year.
        (b)  Where  the  processes or activities normally conducted within the
      space will generate sufficient heat to  produce  the  prescribed  indoor
      temperature during the time of occupancy.
     
                Table 12-1 Minimum Space Temperature Requirements{a}
      ========================================================================
                                                                     Minimum
                                                                   Temperature
                    Rooms or Spaces                                 (degree F)
      ------------------------------------------------------------------------
      Habitable rooms in all buildings                                 70
      Building equipment and machinery rooms                           50
      Patients' rooms, bathrooms and toilet rooms, stairs
        and corridors in hospitals and nursing homes                   75
      Bathrooms and toilet rooms, except patients' bathrooms
        and toilet rooms in hospitals and nursing homes                70
      Offices, waiting rooms, art galleries, museums,
        libraries, meeting rooms, churches, classrooms,
        auditoriums, lecture halls, night clubs, restaurants,
        theatres, locker rooms, dressing rooms, and spaces
        where persons are engaged in sedentary activities              70
      Laboratories, light machine work, product inspections,
        loft buildings, shops, stores, display rooms, show
        rooms, sales rooms, and spaces where persons are
        engaged in moderate physical activities                        70
      Laboratories, light machine work, product inspections,
        loft buildings, shops, stores, display rooms, show
        rooms, sales rooms, and spaces where persons are
        engaged in moderate physical activities                        65
      Gymnasia, dance halls, skating rinks, bowling alleys,
        heavy assembly workrooms or shops, and spaces where
        persons are engaged in vigorous physical activities            60
      Automotive repair shops                                          50
      Storage areas, garages, space where work or process
        requires a low temperature                                   None
      Hospital operating rooms, and recovery, labor, delivery,
        and nursery rooms                                              80
      Swimming pools, bathhouses, and shower rooms                     75
      ========================================================================
     
      Note:
        {a} Where  the listed temperatures differ from those that are required
      to be maintained under the provisions of section 131.03 of the New  York
      city health code, the higher temperature shall apply.