Laws of New York (Last Updated: November 21, 2014) |
ADC New York City Administrative Code(NEW) |
Title 24. ENVIRONMENTAL PROTECTION AND UTILITIES |
Chapter 1. AIR POLLUTION CONTROL |
Subchapter 6. EMISSION STANDARDS |
Section 24-144. Emission of air contaminant; sulfur compounds; volume standard
Latest version.
-
No person shall cause or permit the emission of air contaminant: (a) from equipment used in a manufacturing process if the air contaminant emitted as measured in the flue contains sulfur compounds of more than five hundred parts per million of undiluted process emissions; (b) from a boiler with a capacity of five hundred million Btu per hour or more and completed after August twentieth, nineteen hundred seventy-one, if the air contaminant emitted has a sulfur dioxide content of more than one hundred parts per million by volume of undiluted emissions measured at ten percent excess air; (c) from a boiler with a capacity of five hundred million Btu per hour or more and completed before August twentieth, nineteen hundred seventy-one, if the air contaminant emitted has a sulfur dioxide content of more than two hundred parts per million by volume of undiluted emissions measured at ten percent excess air.